Gwajin Zaɓin Wutar Lantarki - menene ƙarfin wutar lantarki na DC zan nema don gwajin kebul?

 Jun 16, 2026

 Bar sako

 

Q: My megger yana da 500V, 1000V, 2500V, 5000V, da 10kV. Wanne zan zaɓa don LV, MV, da HV?

 

A: Aiwatar da ƙarancin wutar lantarki ba zai haifar da damuwa ba. Da yawa na iya haifar da naushi mai lalacewa{1}} ta. Bi teburin da ya dace.

Daidaitaccen Zaɓin Wutar Lantarki na DC:

Ƙimar Wutar Lantarki na Kebul (U0/U)Insulation ClassNasihar Wutar Lantarki na Gwajin DCIyakar Tsaro (Max)
Ƙananan Ƙarfin Wuta (LV) <0.6/1 kVLow Voltage500V zuwa 1000V DC1000V DC
Matsakaicin Wutar Lantarki (MV) 6/10 zuwa 20/35 kVMatsakaici Voltage2500V ko 5000V DC5000V DC
Babban ƙarfin lantarki (HV) 66 zuwa 220 kV+High Voltage5000V ko 10,000V DC10,000V DC

Me yasa ake amfani da DC don IR? Samar da wutar lantarki na DC baya ci gaba da zana caji mai ƙarfin aiki bayan ƴan daƙiƙa na farko, yana ba da damar auna ƙaramin juzu'in juriya na halin yanzu (micro{0}amps) da ke gudana ta hanyar insulation.

Aika Aikace-aikacen
Aika Aikace-aikacen