Q: My megger yana da 500V, 1000V, 2500V, 5000V, da 10kV. Wanne zan zaɓa don LV, MV, da HV?
A: Aiwatar da ƙarancin wutar lantarki ba zai haifar da damuwa ba. Da yawa na iya haifar da naushi mai lalacewa{1}} ta. Bi teburin da ya dace.
Daidaitaccen Zaɓin Wutar Lantarki na DC:
| Ƙimar Wutar Lantarki na Kebul (U0/U) | Insulation Class | Nasihar Wutar Lantarki na Gwajin DC | Iyakar Tsaro (Max) |
| Ƙananan Ƙarfin Wuta (LV) <0.6/1 kV | Low Voltage | 500V zuwa 1000V DC | 1000V DC |
| Matsakaicin Wutar Lantarki (MV) 6/10 zuwa 20/35 kV | Matsakaici Voltage | 2500V ko 5000V DC | 5000V DC |
| Babban ƙarfin lantarki (HV) 66 zuwa 220 kV+ | High Voltage | 5000V ko 10,000V DC | 10,000V DC |
Me yasa ake amfani da DC don IR? Samar da wutar lantarki na DC baya ci gaba da zana caji mai ƙarfin aiki bayan ƴan daƙiƙa na farko, yana ba da damar auna ƙaramin juzu'in juriya na halin yanzu (micro{0}amps) da ke gudana ta hanyar insulation.